Concrete Foundation for GRP TANK
1. Customers should construct a concrete base according to our designated drawing.
2. The required strength of the base concrete must be at least 180kg/cm.
3. The required width of the each concrete base must be at least 300mm. (Standard 400mm)
4. The width from concrete and next concrete should be 600mm.
For tanks in units of 500 mm, ask for our technical team.(ex. 2,500x3,000x Height)
5. The required width of the between tank and bottom must be at least 500mm for water drainage, tank install, maintenance and repair.
6. The required width of the between tank and wall must be at least 600mm for maintenance and repair.
7. The required width of the between tank top and roof must be at least 1000mm for opening manhole.
8. The thickness of the mortal in the concrete base must not exceed 200mm.
9. Concrete should be integrated with the building structure for safety.
10. The scope of construction is up to the flange fitted to the position to connect the piping.
Consultation is required for perfect piping connection.
11. When installing the PVC flange provided by our company, the thick flange should be fitting to the tank side.
12. customer should piping work after install tank .
(주)에스엠씨
◎주요생산품목 (SMC/GFRP재질 강화플라스틱)
☞ SMC 물탱크(조립식) , 내진 SMC물탱크.
☞ 한전맨홀(지중용 저압접속함체/인입용&간선용)
☞ 통신맨홀 . 소화전맨홀 . 신호등맨홀 , 전기맨홀
본사 : 경기도 김포시 대곶면 율마로194번길6
☎ 031-997 8704 Fax. 031-997 8705
맨홀사업부
☎ 031-989 8710 Fax. 031-989 8705
--------------------------------------------------------------------------
SMC CO.,LTD
Main Product :
- GRP TANK (SMC TANK) . GRP Sectional Panel Water Tank .
- GRP Manhole and Cover
H.Q: 194-6, Yulma-Ro, Daegot-Myun, Gimpo-City, Gyeonggi-Do, South Korea
- Water Tank Dep't : T. +82 31 997 8704 F. +82 31 997 8705
- Manhole Dep't : T. +82 31 989 8705 F. +82 31 989 8705
--------------------------------------------------------------------------